Woodward easYgen-2000 Series User Manual page 247

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
12190
Stop req. in
AUTO
(Stop request in
operation mode
AUTOMATIC)
12540
Start w/o load
(Start without
assuming load )
1795
Startup in
mode
(Operating
mode after
applying the
power supply )
12510
Operat. mode
AUTO
(Activate oper‐
ating mode
AUTOMATIC )
12520
Operat. mode
MAN
(Activate oper‐
ating mode
MANUAL)
37535B
CL
Setting range
Description
[Default]
2
Determined by
If this logical output becomes TRUE, it inhibits all other start processes (e.g.
LogicsManager
Start req. in Auto, emergency power, etc.). Stopping of the engine can be initi‐
ated externally via a discrete input or any logical combination.
[(0 & 1) & 1]
Once the conditions of the LogicsManager have been fulfilled, the control
issues a stop request in AUTOMATIC mode.
Notes
It is possible to interrupt an already activated emergency run.
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
2
Determined by
If this LogicsManager condition is TRUE switching from mains to generator
LogicsManager
supply following an engine start is prevented (the GCB close operation is
blocked).
[(0 & 1) & 1]
This function may be used to perform a test operation. If an emergency power
case occurs meanwhile, it is still possible to change to generator operation.
If this condition becomes TRUE in isolated operation, the GCB cannot be
opened before the MCB has been closed.
Notes
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
2
If the controller is powered down, the unit will start in the following configured
mode when it is powered up again.
[STOP]
The unit starts in the STOP operating mode.
AUTO
The unit starts in the AUTOMATIC operating mode.
MAN
The unit starts in the MANUAL operating mode.
Last
The unit starts in the last operating mode the control was in prior to being de-
energized.
Notes
For the selection of the operating mode via the LogicsManager (if two dif‐
ferent operating modes have been selected simultaneously) the control unit
will prioritize the modes as follows:
n
n
n
2
Determined by
Once the conditions of the LogicsManager have been fulfilled the unit will
LogicsManager
change into operating mode AUTOMATIC.
[(0 & 1) & 1]
If AUTOMATIC mode is selected via the LogicsManager it is not possible to
change operating modes via the front panel.
Notes
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
2
Determined by
Once the conditions of the LogicsManager have been fulfilled the unit will
LogicsManager
change into operating mode MANUAL.
[(0 & 1) & 1]
If MANUAL mode is selected via the LogicsManager it is not possible to
change operating modes via the front panel.
easYgen-2200/2500 | Genset Control
Configure Application > Automatic Run
1. STOP
2. MANUAL
3. AUTOMATIC
Configuration
247