Fig. 237: Write register - clear event
history
6.6.2.7

Remotely Resetting The Default Values

6.6.2.7.1
Modbus Via RS-232/RS-485
Example 1 (enable resetting)
448
Modbus address = 40000 + (Par. ID + 1) = 41707
n
Modbus length = 1 (UNSIGNED 16)
n
Fig. 236: Modscan32 at address 41707
1.
Use the "display options" to set the value format to binary.
2.
Double-click the address to issue a Write Register com‐
mand.
ð Fig. 237 shows how bit 0 is enabled using the Mod‐
Scan32 Software.
The unit can be reset to its default values through the Modbus (via
RS-232 respectively RS-485 ) using the parameters
10417 Ä p. 448
and
detailed in the following steps.
For information on how to use the RS-232 interface via
the service port refer to Ä Chapter 3.2.15 "Service
Port" on page 79.
ID
Parameter
10417
Factory settings via
RS-232
1701
Reset factory default
values
In order to enable the resetting procedure, parameter 10417 must
be enabled.
The resetting procedure via RS-232/RS-485 shall be enabled.
Modbus address = 40000 + (Par. ID + 1) = 410418
n
Modbus length = 1 (UNSIGNED 16)
n
easYgen-2200/2500 | Genset Control
1701 Ä p.
92. The required procedure is
Setting range
Yes / No
Yes / No
Data type
UNSIGNED 16
UNSIGNED 16
37535B