Pulse Suppression Delay Time / Pulse Suppr T_Del; Bi: Dc Braking Activation / Dc Brake Act; Dc Braking Configuration / Dcbrk Config - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Description:
Sets the monitoring time for the standstill identification.
When braking with OFF1 or OFF3, standstill is identified after this time has expired, after the setpoint speed has fallen
below p1226 (also refer to p1145).
Dependency:
The parameter is pre-assigned depending on the size of the power unit.
See also: p1226
NOTICE
For p1145 > 0.0 (RFG tracking) the setpoint is not equal to zero dependent on the selected value. This can therefore
cause the monitoring time in p1227 to be exceeded. In this case, for a driven motor, the pulses are not suppressed.
Note
Standstill is identified in the following cases:
- the speed actual value falls below the speed threshold in p1226 and the time started after this in p1228 has expired.
- the speed setpoint falls below the speed threshold in p1226 and the time started after this in p1227 has expired.
For p1227 = 300.000 s the following applies:
Monitoring is deactivated.
For p1227 = 0.000 s, the following applies:
With OFF1 or OFF3 and a ramp-down time = 0, the pulses are immediately suppressed and the motor "coasts" down.
Once the Control Unit has been booted up for the first time or if the factory settings have been defined accordingly, the
parameter is defined in accordance with the power unit.
p1228

Pulse suppression delay time / Pulse suppr t_del

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the delay time for pulse suppression.
After OFF1 or OFF3, the pulses are canceled, if at least one of the following conditions is fulfilled:
- the speed actual value falls below the threshold in p1226 and the time started after this in p1228 has expired.
- the speed setpoint falls below the threshold in p1226 and the time started after this in p1227 has expired.
Dependency:
See also: p1226, p1227
p1230[0...n]

BI: DC braking activation / DC brake act

CUG120XA_USS (DC
Access level: 2
braking)
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source to activate DC braking.
Dependency:
See also: p1231, p1232, p1233, p1234, r1239
Note
1 signal: DC braking activated.
0 signal: DC braking deactivated.
p1231[0...n]

DC braking configuration / DCBRK config

CUG120XA_USS (DC
Access level: 2
braking)
Can be changed: T, U
Unit group: -
Min:
0
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: -
Unit selection: -
Max:
299.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
14
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 8022
Factory setting:
0.010 [s]
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 7017
Factory setting:
0
Data type: Integer16
Dynamic index: MDS, p0130
Function diagram: 7014, 7016,
7017
Factory setting:
0
495

Advertisement

Table of Contents
loading

Table of Contents