Cu Analog Inputs Wire Breakage Monitoring Delay Time; Cu Analog Inputs Dead Zone / Cu Ai Dead Zone - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Index:
[0] = AI0 (X132 3/4)
[1] = AI1 (X132 10/11)
[2] = NI 1000 0 (X202 80/82)
[3] = NI 1000 1 (X202 81/82)
Dependency:
For the following analog input type, the wire breakage monitoring is active:
p0756[0...1] = 1 (unipolar voltage input monitored (+2 V ... +10 V)), unit [V]
p0756[0...2] = 3 (unipolar current input monitored (+4 mA ... +20 mA)), unit [mA]
p0756[3]: Wire breakage monitoring is not supported for this analog input.
See also: p0756
Note
AI: Analog Input
When p0761 = 0, wire breakage monitoring is not carried out.
X202: IO module terminal
p0762[0...3]
CU analog inputs wire breakage monitoring delay time / CU wire brk t_del
Access level: 3
Can be changed: T, U
Unit group: -
Min:
0 [ms]
Description:
Sets the delay time for the wire breakage monitoring of the analog inputs.
Index:
[0] = AI0 (X132 3/4)
[1] = AI1 (X132 10/11)
[2] = NI 1000 0 (X202 80/82)
[3] = NI 1000 1 (X202 81/82)
Note
AI: Analog Input
X202: IO module terminal
p0764[0...3]

CU analog inputs dead zone / CU AI dead zone

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000
Description:
Determines the width of the dead zone at the analog input.
Analog input type unipolar (e.g. 0 ... +10 V):
The dead zone starts with the characteristic value x1/y1 (p0757/p0758).
Analog input type bipolar (e.g. -10 V ... +10 V):
The dead zone is located at the symmetrical center between characteristic value x1/y1 (p0757/p0758) and x2/y2
(p0759/p0760). The set value doubles the dead zone.
Index:
[0] = AI0 (X132 3/4)
[1] = AI1 (X132 10/11)
[2] = NI 1000 0 (X202 80/82)
[3] = NI 1000 1 (X202 81/82)
Note
AI: Analog Input
X202: IO module terminal
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: -
Scaling: -
Unit selection: -
Max:
1000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max:
20.000
Parameters
7.2 Parameter list
Data type: Unsigned16
Dynamic index: -
Function diagram: 9566, 9568
Factory setting:
100 [ms]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 2251
Factory setting:
0.000
571

Advertisement

Table of Contents
loading

Table of Contents