Current Derating Depending On The Pulse Frequency - Siemens SINAMICS G120 Hardware Installation Manual

Power module
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Technical specifications

7.5 Current derating depending on the pulse frequency

7.5
Current derating depending on the pulse frequency
Article No.
6SL3225-...
-0BE25-5AA0
-0BE27-5AA0
-0BE31-1AA0
-0BE31-5 . A0
-0BE31-8 . A0
-0BE32-2 . A0
-0BE33-0 . A0
-0BE33-7 . A0
-0BE34-5 . A0
-0BE35-5 . A0
-0BE37-5 . A0
60
LO base
LO baseload output current [A] at a pulse frequency of...
load
4 kHz
6 kHz
output
7.5
18.0
12.5
11
25.0
18.1
15
32.0
24.7
18.5
38.0
32.3
22
45.0
38.3
30
60.0
51.0
37
75.0
63.8
45
90.0
76.5
55
110
93.5
75
145
123
90
178
151
8 kHz
10 kHz
12 kHz
11.9
10.6
9.20
17.1
15.2
13.3
23.4
20.8
18.2
26.6
22.8
19.0
31.5
27.0
22.5
42.0
36.0
30.0
52.5
45.0
37.5
63.0
54.0
45.0
77.0
--
--
102
--
--
125
--
--
Hardware Installation Manual, 04/2021, A5E36265179B-AB
14 kHz
16 kHz
7.90
6.60
11.4
9.50
15.6
12.8
17.1
15.2
20.3
18.0
27.0
24.0
33.8
30.0
40.5
36.0
--
--
--
--
--
--
PM250 Power Module

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pm250