Current reduction depending on pulse frequency

Relationship between pulse frequency and output base-load current reduction
Table 13- 9
Rated power
based on LO
The permissible motor cable length depends on the cable type and the chosen pulse frequency.
1
SINAMICS G120C frequency converter
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB
Current reduction depending on pulse frequency
Rated output current at pulse frequency of
4 kHz
0.55 kW
1.7 A
0.75 kW
2.2 A
1.1 kW
3.1 A
1.5 kW
4.1 A
2.2 kW
5.6 A
3.0 kW
7.3 A
4.0 kW
8.8 A
5.5 kW
12.5 A
7.5 kW
16.5 A
11.0 kW
25.0 A
15.0 kW
31.0 A
18.5 kW
37.0 A
13.9 Current reduction depending on pulse frequency
6 kHz
8 kHz
10 kHz
1.4 A
1.2 A
1.0 A
1.9 A
1.5 A
1.3 A
2.6 A
2.2 A
1.9 A
3.5 A
2.9 A
2.5 A
4.8 A
3.9 A
3.4 A
6.2 A
5.1 A
4.4 A
7.5 A
6.2 A
5.3 A
10.6 A
8.8 A
7.5 A
14.0 A
11.6 A
9.9 A
21.3 A
17.5 A
15.0 A
26.4 A
21.7 A
18.6 A
31.5 A
25.9 A
22.2 A
Technical data
1
12 kHz
14 kHz
0.9 A
0.8 A
1.1 A
1.0 A
1.6 A
1.4 A
2.1 A
1.8 A
2.8 A
2.5 A
3.7 A
3.3 A
4.4 A
4.0 A
6.3 A
5.6 A
8.3 A
7.4 A
12.5 A
11.3 A
15.5 A
14.0 A
18.5 A
16.7 A
16 kHz
0.7 A
0.9 A
1.2 A
1.6 A
2.2 A
2.9 A
3.5 A
5.0 A
6.6 A
10.0 A
12.4 A
14.8 A
307