Ci: Torque Limit Lower / M_Max Lower; Co: Torque Limit Upper/Motoring Scaling / M_Max Up/Mot Scal; Co: Torque Limit Lower Scaling / M_Max Lower Scal - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Dependency:
See also: p1520, p1521, p1523
DANGER
Negative values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
p1523[0...n]

CI: Torque limit lower / M_max lower

Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source for the lower torque limit.
Dependency:
See also: p1520, p1521, p1522
DANGER
Positive values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
p1524[0...n]

CO: Torque limit upper/motoring scaling / M_max up/mot scal

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-2000.0 [%]
Description:
Sets the scaling for the upper torque limit or the torque limit when motoring.
Dependency:
p1400.4 = 0: upper/lower
p1400.4 = 1: motoring / regenerating
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note
This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
p1525[0...n]

CO: Torque limit lower scaling / M_max lower scal

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-2000.0 [%]
Description:
Sets the scaling for the lower torque limit.
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note
This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: p2003
Unit selection: -
Max:
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
2000.0 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
2000.0 [%]
Parameters
7.3 Parameters
Data type: Unsigned32 /
FloatingPoint32
Dynamic index: CDS, p0170
Function diagram: 6020, 6630
Factory setting:
1521[0]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 5620, 5630
Factory setting:
100.0 [%]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 6630
Factory setting:
100.0 [%]
525