Setting the automatic restart function

Functionality
After a power failure (F3 "Undervoltage"), the automatic restart function (enabled using
P1210) automatically switches on the motor if an ON command is active. Any faults are
automatically acknowledged by the converter.
When it comes to power failures (line supply failure), then a differentiation is made between
the following conditions:
● "Line undervoltage (mains brownout)" is a situation where the line supply is interrupted
and returns before the built-in BOP display has gone dark (this is an extremely short line
supply interruption where the DC link hasn't completely collapsed).
● "Line failure (mains blackout)" is a situation where the built-in BOP display has gone dark
(this represents a longer line supply interruption where the DC link has completely
collapsed) before the line supply returns.
Setting parameters
Parameter Function
P1210
Automatic
restart
P1211
Number of
restart at-
tempts
P1214
Restart time
interval
120
Setting
This parameter configures automatic restart function.
= 0: Disabled
= 1: Trip reset after power on, P1211 disabled
= 2: Restart after mains blackout, P1211 disabled
= 3: Restart after mains brownout or fault, P1211 enabled
= 4: Restart after mains brownout, P1211 enabled
= 5: Restart after mains blackout and fault, P1211 disabled
= 6: Restart after mains brown- /blackout or fault, P1211 enabled
= 7: Restart after mains brown- /blackout or fault, trip when P1211 expires
= 8: Restart after mains brown- /blackout with F3 and leave an interval in seconds determined
by P1214, P1211 disabled
= 9: Restart after mains brown- /blackout with F3 during the attempt time determined by P1214,
P1211 disabled
= 10: Restart after mains brown- /blackout with F3 during the attempt time determined by P1214
or manual fault acknowledgement, P1211 disabled
This parameter specifies number of times converter will attempt to restart if automatic restart
P1210 is activated.
Range: 0 to 10 (factory default: 3)
This parameter has either of the following functions:
Specifying the restart interval when P1210 = 8
Specifying the total restart attempt time when P1210 = 9 or P1210 = 10
Range: 0 to 1000 (factory default: 30)