Automatic Restart - Siemens SINAMICS Series Operating Instructions Manual

Hide thumbs Also See for SINAMICS Series:
Table of Contents

Advertisement

Descriptions of functions

10.26 Automatic restart

10.26
Automatic restart
"Automatic restart" means:
When brief interruptions in the network (such as voltage dips) occur, the SINAMICS DC
MASTER does not enter the "FAULT" operating state immediately, but instead blocks the
armature firing pulses before automatically re-enabling them once the network returns to
normal.
"Brief" refers to a time that is: shorter than the time set at p50086 (= hot restart time)
During the brief pulse inhibit period that is initiated when faults occur in the network, the
SINAMICS DC MASTER waits in operating state o4.0 (for power system faults in the
armature circuit) or o5.1 (for power system faults in the field circuit).
If the network does not return to normal during the hot restart time, the relevant fault is
triggered as soon as it elapses.
The following faults relate to the "Automatic restart" function:
F60004
F60005
F60006
F60007
F60008
F60009
Note
There is no automatic restart when the electronics power supply fails.
10.27
Operation on a single-phase line supply
SINAMICS DCM converters can also be operated on single-phase line supplies.
Fields of application for this operating mode include:
● Replacement of older single-phase converters employing analog technology
● Plants and systems where there is no 3-phase line supply
● Presenting and demonstrating SINAMICS DCM in seminar hotels and demonstration
rooms where generally there is no three-phase line supply
Note
For single-phase operation, dynamic overload of the devices is not possible. The I
monitoring must be deactivated (p50075=0). If the I
phase operation, fault 60058 is output with fault value 4.
598
Armature circuit phase failure (1U1, 1V1, 1W1)
Field circuit phase failure (3U1, 3W1)
Undervoltage (armature current or field current)
Overvoltage (armature current or field current)
Line frequency too low (armature current or field current)
Line frequency too high (armature current or field current)
t monitoring is activated, for single-
2
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
t
2

Advertisement

Table of Contents
loading

Table of Contents