p1212

Automatic restart delay time start attempts / AR t_wait start

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.1 [s]
Description:
Sets the delay time up to restart.
Dependency:
This parameter setting is active for p1210 = 4, 6, 26.
For p1210 = 1, the following applies:
Faults are only automatically acknowledged in half of the waiting time, no restart.
See also: p1210
NOTICE
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
Note
The faults are automatically acknowledged after half of the delay time has expired and the full delay time.
If the cause of a fault is not removed in the first half of the delay time, then it is no longer possible to acknowledge in
the delay time.
p1213[0...1]

Automatic restart monitoring time / AR t_monit

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.0 [s]
Description:
Sets the monitoring time of the automatic restart (AR).
Index:
[0] = Restart
[1] = Reset start counter
Dependency:
See also: p1210
NOTICE
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
After fault F07320 occurs, the switch-on command must be withdrawn and all of the faults acknowledged so that the
automatic restart function is re-activated.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: -
Unit selection: -
Max:
1000.0 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
10000.0 [s]
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
1.0 [s]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
[0] 60.0 [s]
[1] 0.0 [s]
493