5.4.5

Adapting the encoder data

Preconditions
● You have selected an encoder type that does not precisely match your encoder, because
it is not included in the list of default encoder types.
● You have completely configured the drive.
Procedure with STARTER
Proceed as follows to adapt the encoder data:
1. Select the "Motor encoder" screen form.
2. Select the "Encoder data" button.
3. You have access to the following settings in the "Encoder data" screen form:
– You can change all of the encoder data.
– You can select another encoder. In this screen form, STARTER only lists the encoder
If you wish to set another encoder interface, then you must reconfigure the inverter.
You have adapted the encoder data.
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
types, which are permitted for the configured interface.
Commissioning
5.4 Basic commissioning using a PC
81