Operation
8.1 Operation
3 Expert
4 Service
8.1.1.2

Data sets

CDS: Command data set
The BICO parameters (binector and connector inputs) are grouped together in a command
data set. These parameters are used to interconnect the signal sources of a SINAMICS
DCP.
By parameterizing several command data sets and switching between them, the SINAMICS
DCP can be operated with different preconfigured signal sources.
A command data set contains the following (examples):
● Binector inputs for control commands (digital signals)
– ON/OFF, enable signals (p0844, etc.)
One drive object can manage two command data sets.
The following parameters are available for selecting command data sets and for displaying
the currently selected command data set:
● Binector input p0810 BI: Command data set (CDS) selection
● r0836: Displays the selected data set
Example: Switchover between command data set 0 and 1
Image 8-2
DDS: Drive data set
Drive data sets are not used with the SINAMICS DCP.
110
Access level
Expert knowledge is already required for these parameters
(e.g. knowledge of assigning BICO parameters).
Please contact your local Siemens office for the password for parameters
with access level 4 (Service). It must be entered into p3950.
Switching over the command data set (example)
Remark
Operating Instructions, 05/2016, A5E34382853K