Parameters
7.3 Parameters
r0080[0...1]
CO: Torque actual value / Actual torque
Access level: 3
Can be changed: -
Unit group: 7_1
Min:
- [Nm]
Description:
Display and connector output for actual torque value.
Index:
[0] = Unsmoothed
[1] = Smoothed with p0045
Dependency:
See also: r0031, p0045
Note
The value is available smoothed (r0031 with 100 ms, r0080[1] with p0045) and unsmoothed (r0080[0]).
r0082[0...2]
CO: Active power actual value / P_act
Access level: 3
Can be changed: -
Unit group: 14_5
Min:
- [kW]
Description:
Displays the instantaneous active power.
Index:
[0] = Unsmoothed
[1] = Smoothed with p0045
[2] = Electric power
Dependency:
See also: r0032
Note
The mechanical active power is available smoothed (r0032 with 100 ms, r0082[1] with p0045) and unsmoothed
(r0082[0]).
r0087
CO: Actual power factor / Cos phi act
Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Displays the actual active power factor.
This value refers to the electrical power of the basic fundamental signals at the output terminals of the converter.
p0096
Application class / Appl_class
Access level: 1
Can be changed: C2(1)
Unit group: -
Min:
0
Description:
Setting the commissioning and control view for various application classes.
Value:
0:
1:
2:
374
Expert
Standard Drive Control (SDC)
Dynamic Drive Control (DDC)
Calculated: -
Scaling: p2003
Unit selection: p0505
Max:
- [Nm]
Calculated: -
Scaling: r2004
Unit selection: p0505
Max:
- [kW]
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
2
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6714, 6799
Factory setting:
- [Nm]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6714, 6799
Factory setting:
- [kW]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
-
Data type: Integer16
Dynamic index: -
Function diagram: 6019
Factory setting:
0
SINAMICS G120XA converter