General Inverter Behavior When In The Profienergy Energy-Saving Mode; Settings And Displays For Profienergy In The Inverter - Siemens SIMATIC ET 200pro Series Operating Instructions Manual

Low voltage converter for the distributed i/o system
Hide thumbs Also See for SIMATIC ET 200pro Series:
Table of Contents

Advertisement

PROFIenergy - saving energy with SIMATIC S7
(https://support.industry.siemens.com/cs/ww/en/view/41986454)
7.19.1

General inverter behavior when in the PROFIenergy energy-saving mode

● When the PROFIenergy energy-saving mode is active, the inverter issues alarm A08800.
● When the PROFIenergy energy-saving mode is active, the inverter does not send any
diagnostic alarms.
● If the bus connection to the control system is interrupted while the inverter is in the
energy-saving mode, the inverter exits the energy-saving mode and resumes normal
operation.
● The inverter changes into normal operation if the control system goes into the stop
condition while the inverter is in the energy-saving mode.
PROFIenergy energy-saving mode 2
Parameter r5600 shows the active PROFIenergy energy-saving mode.
Connector parameter r5613 indicates whether the PROFIenergy energy-saving mode is
active. You can set additional responses using these parameters.
7.19.2

Settings and displays for PROFIenergy in the inverter

Pause time
● Minimum pause time: p5602
– When the pause time, which is sent using command "Start_Pause", is equal to or
– When the pause time is less than p5602[1], the inverter rejects the command
● Maximum pause time: p5606
Inhibiting PROFIenergy
If you set p5611.0 = 1, you block the response of the inverter to PROFIenergy control
commands. In this case, the inverter rejects the "Start_Pause" command with 50 hex (no
appropriate pause mode).
Transition into the energy-saving mode from the PROFIdrive states ready (S3) and operation (S4)
If you set p5611.2 = 1, you allow the transition into the energy-saving mode from the
PROFIdrive states ready (S3) and operation (S4).
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257324B AE
greater than the value in p5602[1], then the inverter goes into the energy-saving
mode.
"Start_Pause" with 50 hex (no appropriate pause mode).
Advanced commissioning
7.19 PROFIenergy profile for PROFINET
175