Operation
6.9 Communication via PROFINET IO
6.9.6.4
PROFIenergy measured values
Table 6- 31
Overview of the PROFIenergy measured values
PROFIenergy measured
value
ID
Name
34
Active power
166
Power factor
200
Active energy
import
6.9.6.5
PROFIenergy energy-saving mode
The drive devices support PROFIenergy energy-saving mode 2. The following two
parameters indicate the effective PROFIenergy mode:
● Parameter r5600 indicates the currently active PROFIenergy mode.
● Using interconnectable bits, the r5613 parameter indicates whether the PROFIenergy
energy saving is active.

Activating the energy saving mode

The energy-saving mode can activated or deactivated for the drive devices using the
PROFIenergy control commands (see also PROFIenergy commands).
General converter behavior when in the PROFIenergy energy-saving mode
● When the PROFIenergy energy-saving mode is active, the converter issues alarm
A08800.
● When the PROFIenergy energy-saving mode is active, the converter does not send any
diagnostic alarms.
● When the PROFIenergy energy-saving mode is active, then the READY-LED flashes
green in the on / off ratio: 500 ms on, 3000 ms off.
● If the bus connection to the control system is interrupted while the converter is in the
energy-saving mode, the converter exits the energy-saving mode and resumes normal
operation ("ready_to_operate").
● The converter changes into normal operation if the control system goes into the stop
condition while the converter is in the energy-saving mode.
384
PROFIenergy accuracy
Domain
Class
1
12
1
12
2
11
Unit
SINAMICS source parameters
Parameter
Name
W
r0032
Active power
smoothed
1
r0038
Smoothed
power factor
Wh
r0039[1]
Energy
accepted
Operating Instructions, 12/2018, A5E36652151A
Value range
Largest value for
r2004 of all drive
objects
0 ... 1
-