6.5

Resetting the safety function parameters to the factory setting

Procedure
To reset the safety function settings to the factory setting without changing the standard
settings, proceed as follows:
1. Go online with STARTER
2. Open the screen form for the safety functions
3. Press the button to restore the factory settings
4. Enter the password,for the safety functions.
5. Confirm saving parameters (RAM to ROM).
6. Go offline with STARTER .
7. Switch off the inverter supply voltage.
8. Wait until all LED on the inverter go dark. Now switch on the inverter supply voltage again
(power on reset).
You have restored the safety functions in the inverter to the factory settings.
Parameters Description
p0010
p9761
p9762
p9763
p0970
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257324B AE
6.5 Resetting the safety function parameters to the factory setting
Drive, commissioning parameter filter
0
Ready
30
Parameter reset
Enter a password (factory setting: 0000 hex)
Permissible passwords lie in the range 1 ... FFFF FFFF.
New password
Password confirmation
Confirming the new Safety Integrated password.
Reset drive parameters
5
Starts a safety parameter reset.
After the reset, the inverter sets p0970 = 0.
.
.
Commissioning
77