4.2
Parameters
4.2.1
Parameters of the Frequency Converter
The parameter names listed in bold in the tables are explained in further detail in
Section 4.2.2.
Table 4-5
Parameters of the Frequency Converter
Parameters
Reaction to
CPU-/master-STOP
Diagnostic interrupt
Operation in
Europe/USA
Rated frequency of motor
Rated voltage of motor
Rated current of motor
Rated speed of motor
Rated power of motor
Thermistor monitoring
of motor
EM 148-FC Frequency Converter
A5E00065321-03
Possible settings
Rapid stop
Ramp down
Coast to a standstill
Keep last value
Disable
Enable
EUR
USA
50 Hz
60 Hz
120 V
230 V
400 V
460 V
500 V
0.1 ... 4.0 A
(resolution 0.1 A)
–1
0 ... 5000 min
–1
(resolution 20 min
)
0.1... 1.5 kW or
0.1... 2.00 hp (resolution
0.01 kW or hp)
Disable
Enable
Functions and Technical Specifications
Parameter values via
DDB file
1 ... 40 (* 0.1 A)
–1
0 ... 250 (* 20 min
)
0.1... 150 (* 0.01 kW) or
0.1... 200 (* 0.01 hp)
Default
Coast to a
standstill
Disable
EUR
50 Hz
400 V
4.0 A
–1
1400 min
1.5 kW or 2 hp
Disable
4-7