Command Sources; Profidrive" Default Setting - Siemens SINAMICS S150 Operating Instructions Manual

Converter cabinet units 75 kw to 1200 kw
Hide thumbs Also See for SINAMICS S150:
Table of Contents

Advertisement

6.4

Command sources

6.4.1

"Profidrive" default setting

Requirements
The "PROFIdrive" default setting was chosen during commissioning:
• STARTER:
• AOP30:
Command sources
Figure 6-9
Priority
The command source priorities are shown in the diagram "Command sources - AOP30 ←→
PROFIdrive".
Note
The EMERGENCY STOP and motor protection signals are always active (regardless of the
command source).
All of the supplementary setpoints are deactivated for LOCAL master control.
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
"PROFIdrive"
"5: PROFIdrive"
Command sources - AOP30 ←→ PROFIdrive
Operation
6.4 Command sources
187