Parameters
7.2 Parameter list
r0965

PROFIdrive profile number / PD profile number

G120X_DP,
Access level: 3
G120X_PN
Can be changed: -
Unit group: -
Min:
-
Description:
Displays the PROFIdrive profile number and profile version.
Constant value = 0329 hex.
Byte 1: Profile number = 03 hex = PROFIdrive profile
Byte 2: Profile version = 29 hex = Version 4.1
Note
When the parameter is read via PROFIdrive, the Octet String 2 data type applies.
p0969

System runtime relative / t_System relative

Access level: 3
Can be changed: T
Unit group: -
Min:
0 [ms]
Description:
Displays the system runtime in ms since the last POWER ON.
Note
The value in p0969 can only be reset to 0.
The value overflows after approx. 49 days.
When the parameter is read via PROFIdrive, the TimeDifference data type applies.
p0970

Reset drive parameters / Drive par reset

Access level: 1
Can be changed: C2(1, 30)
Unit group: -
Min:
0
Description:
The parameter is used to initiate the reset of the drive parameters.
Parameters p0100, p0205 are not reset.
The following motor parameters are defined in accordance with the power unit: p0300 ... p0311.
Value:
0:
1:
3:
10:
11:
12:
30:
100:
300:
NOTICE
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
602
Inactive
Start a parameter reset
Start download of volatile parameters from RAM
Start loading the parameters saved with p0971=10
Start loading the parameters saved with p0971=11
Start loading the parameters saved with p0971=12
Start loading the delivery state saved with p0971=30
Start a BICO interconnection reset
Only Siemens internal
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
4294967295 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max:
300
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
-
Data type: Unsigned32
Dynamic index: -
Function diagram: 8050, 8060
Factory setting:
0 [ms]
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
0