X522 Analog Outputs/Temperature Sensor - Siemens SINAMICS DCM Operating Instructions Manual

Dc converter
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Additional system components
7.4 Terminal Module TM31
7.4.3.6

X522 analog outputs/temperature sensor

Table 7- 31
X522 terminal strip
Terminal
1
2
3
4
5
6
7
8
AO xV: Analog output voltage; AO xC: Analog output current
1)
CAUTION
Permissible back-EMF at the outputs: ±15 V
NOTICE
The KTY temperature sensor must be connected with the correct polarity.
Hazard due to electric shock
Only temperature sensors that meet the protective separation specifications in EN 61800-5-
1 may be connected to terminals "+Temp" and "-Temp".
There is a risk of electric shock if this is not carefully observed.
210
Designation
1)
AO 0V+
AO 0-
AO 0C+
AO 1V+
AO 1-
AO 1C+
+ Temp
- Temp
DANGER
Technical specifications
You can set the following output signals using parameters:
Voltage: -10 to 10 V (max. 3 mA)
Current 1: 4 to 20 mA (max. load resistance ≤ 500 Ω)
Current 2: -20 to 20 mA (max. load resistance ≤ 500 Ω)
Current 3: 0 to 20 mA (max. load resistance ≤ 500 Ω)
Resolution: 11 bits + sign
Continuous short-circuit proof
Temperature sensor KTY84-1C130/PTC
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619