Functions, Monitoring, and Protective Functions
9.4 Monitoring and protective functions
9.4.5.3

Temperature sensor connection at a Sensor Module (option K50)

Temperature measurement via KTY
The device is connected to the appropriate terminals Temp- and Temp+ on the Sensor
Module in the forward direction of the diode (see corresponding section in chapter "Electrical
installation").
● Activate motor temperature measurement via encoder 1: p0600 = 1.
● Set the KTY temperature sensor type: p0601 = 2
Temperature measurement via PTC
The device is connected to the appropriate terminals Temp- and Temp+ on the Sensor
Module (see corresponding section in chapter "Electrical installation"). The threshold for
changing over to an alarm or fault is 1650 Ω.
● Activate motor temperature measurement via encoder 1: p0600 = 1.
● Set the PTC temperature sensor type: p0601 = 1
9.4.5.4

Temperature sensor connection directly at the Control Interface Module

Temperature measurement via KTY
The device is connected to terminals X41:3 (Temp-) and X41:4 (Temp+) on the Control
Interface Module in the forward direction of the diode.
● Activate motor temperature measurement via Motor Module: p0600 = 11.
● Set the KTY temperature sensor type: p0601 = 2
Temperature measurement via PTC
The connection is made at the terminals X41:3 (Temp-) and X41:4 (Temp+) at the Control
Interface Module. The threshold for changing over to an alarm or fault is 1650 Ω.
● Activate motor temperature measurement via Motor Module: p0600 = 11.
● Set the PTC temperature sensor type: p0601 = 1
Temperature measurement using the bimetal normally closed contact
The connection is made at the terminals X41:3 (Temp-) and X41:4 (Temp+) at the Control
Interface Module. The threshold for changing over to an alarm or fault is 100 Ω.
● Activate motor temperature measurement via Motor Module: p0600 = 11.
● Set the temperature sensor type bimetal normally closed contact: p0601 = 4
502
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A