Commissioning
5.7 Basic parameterization of the drive objects
5.7.2.3

Line supply data / Operating mode

Overview
You set the most important parameters for the operation of an infeed in the function view of the
"Line data / operating mode" screen form. The corresponding parameters are displayed
depending on the infeed type.
Figure 5-8
The representation of this screen form is dependent upon the respective Line Module being
used:
Setting
Device supply voltage
DC-link voltage setpoint de‐
fault setting
Supply/DC-link identification
Operating mode for ALM
208
Example: line supply data/operating mode for an Active Line Module
ALM
SLM
BLM
x
x
x
x
x
x
x
Explanation
x
The value in this field (p3510) is determined automati‐
cally from the defined operating voltage.
If the line supply / DC-link identification has already
been performed once, then the value is preset to "OFF".
Presetting of the operating mode is dependent upon
the operating voltage of the ALM:
> 415 V
= Udc Unregulated (Smart Mode) active
eff
≤ 415 V
= Udc Regulated (Active Mode) active
eff
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2
Commissioning with Startdrive