Resonance Damping - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Setpoint channel and closed-loop control
7.3 V/f control
7.3.2

Resonance damping

Description
Resonance damping damps oscillations in the active current, which often occur during no-
load operation. Resonance damping is active in the range between approximately 5% and
90% of the rated motor frequency (p0310), up to 45 Hz at most, however.
Figure 7-9
Note
At p1349 = 0 the switching limit is automatically set to 95% of the rated motor frequency, up
to 45 Hz at most, however.
Function diagram
FP 6310
Parameters
• r0066
• r0078
• p1338
• p1339
• p1349
382
Resonance damping
Resonance damping and slip compensation
Output frequency
torque-generating actual current value
Resonance damping gain
Resonance damping filter time constant
Resonance damping maximum frequency
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A