Figure 152
Test setup for In-band OSNR testing
Example:
•
OSNR measured with in-band OSA-500R or OSA-500RS at terminal site (1)
provides value of 14dB
•
Service failed as the OSNR is < 20 dB
How to locate the failure?
Perform the following tests at EDFA monitor access points (2-5):
•
Check per channel input and output power of EDFA
=> Input power must be in the system specified range
•
Check power uniformity
=> Equal power levels for all channels at EDFA output
•
Compare OSNR from EDFA to EDFA
=> OSNR may decrease because of the amplifier noise figure NF (type 3-4 dB)
per EDFA
•
Locate and exchange optical amplifier
Measurement of I-OSNR
Pre-setting the OSA for an in-band OSNR
measurement in I-OSNR mode
As the out-of-band OSNR measurements might not provide the 'TRUE' OSNR value for
the above listed systems configurations, the in-band OSNR measurement method
based on Viavi's polarization nulling technique must be selected.