8.4.5

Fixed speed as setpoint source

In many applications after switching on the motor, all that is needed is to run the motor at a
constant speed or to switch between different speeds.
Example: After it has been switched on, a conveyor belt only runs with two different
velocities.
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Extended setup of motorized potentiometer
Description
MOP configuration (factory setting: 00110 bin)
.00
Storage active
= 0: After the motor has been switched on, the setpoint = p1040
= 1: After the motor has switched off, the inverter saves the setpoint. After the
motor has switched on, the setpoint = the stored value
.01
Automatic mode, ramp-function generator active (1-signal via BI: p1041)
= 0: Ramp-up/ramp-down time = 0
= 1: With ramp-function generator
In manual mode (p1041 = 0), the ramp-function generator is always active.
.02
Initial rounding active
1: With initial rounding. Using the initial rounding function it is possible to enter
very small setpoint changes
.03
Storage in NVRAM active
1: If bit 00 = 1, the setpoint is retained during a power failure
.04
Ramp-function generator always active
1: The inverter also calculates the ramp-function generator when the motor is
switched off
MOP maximum speed (factory setting: 0 rpm)
Automatically pre-assigned when commissioning
MOP minimum speed (factory setting: 0 rpm)
Automatically pre-assigned when commissioning
Motorized potentiometer, inversion (factory setting: 0)
Signal source for inverting the minimum speed / velocity or maximum speed / velocity
Motorized potentiometer, manual/automatic (factory setting: 0)
Signal source for switchover from manual to automatic
Motorized potentiometer, accept setting value (factory setting: 0)
Signal source for accepting the setting value. The motorized potentiometer accepts
the setting value p1044 on signal change p1043 = 0 → 1.
MOP setting value (factory setting: 0)
Signal source for the setting value.
Functions
8.4 Setpoint sources
173