206050
<location>Infeed: Smart Mode not supported
Message value:
-
Drive object:
AFE_SINUMERIK_828, SIC_COMBI, SIC_SINUMERIK_828
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The power unit does not support the Smart Mode.
Remedy:
- set the suitable sampling time 250 µs <= p0115[0] <= 400 µs (e.g. by setting p0112 and p0115 to the factory setting).
- upgrade the power unit software and/or hardware for the Smart Mode. The availability of the Smart Mode function is
displayed in r0192.
- for A_INF the following applies: De-activate the Smart Mode with p3400.0 = 0 and activate the voltage control with
p3400.3 = 1. For booksize power units, it must be noted that for a supply voltage p0210 > 415 V only the Smart Mode
is possible in the pre-setting. If DC link voltages above 660 V are permissible in the application, then voltage-controlled
operation can be activated with p0280, p0210, p3400 and p3510. The information regarding p0210 should be carefully
noted.
See also: r0192 (Power unit firmware properties)
206052
<location>Infeed: Filter temperature evaluation not supported
Message value:
-
Drive object:
AFE_SINUMERIK_828, SIC_COMBI, SIC_SINUMERIK_828
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
The power unit does not support filter temperature evaluation.
This feature (r0192.11) is required when an Active Interface Module is used as a line filter (p0220 = 41 ... 45).
Remedy:
Upgrade the firmware for the power unit to a later version.
See also: r0192 (Power unit firmware properties), p0220 (Infeed line filter type)
206100
<location>Infeed: Shutdown due to line supply undervoltage condition
Message value:
%1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SIC_COMBI, SIC_SINUMERIK_828
Reaction:
OFF2 (OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The filtered (steady-state) value of the line supply voltage is less than the fault threshold (p0283).
Fault condition: Vrms < p0283 * p0210
Fault value (r0949, floating point):
Actual steady-state line supply voltage.
See also: p0283 (Line supply undervoltage, shutdown (trip) threshold)
Remedy:
- check the line supply.
- check the line supply voltage (p0210).
- check the fault threshold (p0283).
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
SINAMICS alarms
621