Cause:
The Terminal Module was not successfully initialized.
Alarm value (r2124, interpret hexadecimal):
01: TM17 or TM41 - incorrect configuration request.
02: TM17 or TM41 - programming not successful.
04: TM17 or TM41 - invalid time stamp
Remedy:
Carry out a POWER ON.
235910
<location>TM: Module overtemperature
Message value:
-
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828, TM120
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature in the module has exceeded the highest permissible limit.
Remedy:
- reduce the ambient temperature.
- replace the Terminal Module.
235911
<location>TM: Clock synchronous operation sign-of-life missing
Message value:
-
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828, TM120
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum permissible number of errors in the master sign-of-life (clock synchronous operation) has been
exceeded in cyclic operation.
When the alarm is output, the module outputs are reset up to the next synchronization.
Remedy:
- check the physical bus configuration (terminating resistor, shielding, etc.).
- check the interconnection of the master sign-of-life (r4201 via p0915).
- check whether the master correctly sends the sign-of-life (e.g. set up a trace with r4201.12 ... r4201.15 and trigger
signal r4301.9).
- check the bus and master for utilization level (e.g. bus cycle time Tdp was set too short).
235920
<location>TM: Error temperature sensor channel 1
Message value:
%1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828, TM120
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, interpret decimal):
1: Wire breakage or sensor not connected (KTY: R > 1630 Ohm).
2: Measured resistance too low (PTC: R < 20 Ohm, KTY: R < 50 Ohm).
Remedy:
- make sure that the sensor is connected correctly.
- replace the sensor.