4632
Logical PROFIBUS handwheel slot base address for handwheel %1 not found
Parameters:
%1 = Handwheel number
Definitions:
For PROFIBUS/PROFINET only:
The logical basic address of the PROFIBUS handwheel slot in machine data array
$MN_HANDWHEEL_LOGIC_ADDRESS[] indexed in machine data $MN_HANDWHEEL_MODULE was not found in
the current STEP 7 hardware configuration.
Reaction:
Interface signals are set.
Alarm display.
Remedy:
Check if MD11351 $MN_HANDWHEEL_MODULE of the corresponding handwheel is correct. Check if indexed logical
base address of PROFIBUS handwheel slot in machine date array MD11353
$MN_HANDWHEEL_LOGIC_ADDRESS[] is correct.
Program
Switch control OFF - ON.
Continuation:
5000

Communication job not executable %1

Parameters:
%1 = Reference to which resources are no longer available.
Definitions:
The communication job (data exchange between NCK and HMI, e.g.: loading an NC part program) cannot be executed
because there is insufficient memory space. Cause: too many communication jobs in parallel.
Reaction:
Alarm display.
Remedy:
- Reduce the number of communication jobs taking place at the same time or increase MD10134
$MN_MM_NUM_MMC_UNITS
- Restart communication job.
Please inform the authorized personnel/service department. No remedial measures are possible - the operation trig-
gering the alarm message has to be repeated. Clear the alarm display with Cancel.
Program
Clear alarm with the Delete key or NC START.
Continuation:
6000

Memory reorganized using standard machine data

Definitions:
The memory management was not able to allocate the NC user memory with the values in the machine data. It did
not have enough memory available because the total memory available is provided as dynamic and static memory for
the NC user (e.g. for macro definitions, user variables, number of tool offsets, number of directories and files etc.).
Reaction:
NC not ready.
Mode group not ready, also effective for single axes.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Redefine the NC memory structure!
A specific MD for NC user memory allocation cannot be stated to be the cause of the alarm. The MD initiating the alarm
therefore has to be determined on the basis of the default values in the machine data by changing the user-specific
memory structure step by step.
Usually, it is not just one single MD that has been set too large. Therefore it is advisable to reduce the memory area
by a certain proportion in several MDs.
Program
Teileprogramm neu starten.Clear alarm with the RESET key in all channels of this mode group. Restart part program.
Continuation:
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
NCK alarms
47