SINAMICS alarms
201512
<location>BICO: No scaling available
Message value:
%1
Drive object:
All objects
Reaction:
Servo: OFF2
Infeed: OFF2 (OFF1)
Acknowledge:
POWER ON
Cause:
An attempt was made to determine a conversion factor for a scaling that does not exist.
Fault value (r0949, interpret decimal):
Unit (e.g. corresponding to SPEED) for which an attempt was made to determine a factor.
Remedy:
Apply scaling or check the transfer value.
201513
<location>BICO: Spanning DO between different scalings
Message value:
Parameter: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested interconnection was established. However, a conversion is made between the BICO output and BICO
input using the reference values.
An interconnection is made between different drive objects and the BICO output has different normalized units than
the BICO input or the normalized units are the same but the reference values are different.
Example:
The BICO output has, as standard unit, voltage and the BICO input has current; both lie in different drive objects.
This means that the factor p2002 (contains the reference value for current) / p2001 (contains the reference value for
voltage) is calculated between the BICO output and BICO input.
Fault value (r0949, interpret decimal):
Parameter number of the BICO input (signal sink).
Remedy:
None necessary.
201514
<location>BICO: Error when writing during a reconnect
Message value:
Parameter: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
During a reconnect operation (e.g. while booting or downloading - but can also occur in normal operation) a parameter
was not able to be written to.
Example:
When writing to a double word BICO input in the second index, the memory areas overlap (e.g. p8861). The parameter
is then reset to the factory setting.
Alarm value (r2124, interpret decimal):
Parameter number of the BICO input (signal sink).
Remedy:
None necessary.