HMI alarms
120006
The channel switchover is currently disabled by area %1.
Parameters:
%1 = Operating area name
Definitions:
The area %1 has disabled the channel switchover at the moment, as it is performing a critical operation (e.g. execution
from external sources, etc.), during which no channel switchover may occur.
Reaction:
Alarm display.
Remedy:
Wait until the critical operation is finished or end the critical operation manually.
Program
Internal
Continuation:
120007
The channel switchover is currently disabled.
Definitions:
The channel switchover is currently disabled, as a critical operation, during which no channel switchover may occur,
is being carried out.
Reaction:
Alarm display.
Remedy:
Wait until the critical operation is finished or end the critical operation manually.
Program
Internal
Continuation:
120008
Control unit switchover, PLC timeout: %1
Parameters:
%1 = --
Definitions:
001: MMC would like to go offline from this NCU. MMC has made the offline request in the online PLC and is waiting
for the positive / negative acknowledgement from the PLC.
002: MMC would like to go online to this NCU. MMC has called the target PLC and is waiting for the release to go
online.
003: MMC has requested the active operating mode and is waiting for acknowledgement from the PLC.
Remedy:
Check whether the switchover blocks are loaded and started in the online PLC.
120200
Image preparation suppressed
Definitions:
The control is so heavily loaded by the processing of a subroutine, that it cannot keep all the display values up-to-date.
Reaction:
Alarm display.
Remedy:
The alarm disappears automatically as soon as the overload situation has been eliminated.
If this alarm occurrs often, the start-up engineer will have to take appropriate measures (e.g. reduce IPO clock pulse
rate).
Program
Internal
Continuation:
Alarms
Diagnostics Manual 07/2010, 6FC5398-8BP40-0BA0
3