202030
<location>Function generator: Physical address equals zero
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The specified physical address is zero.
See also: p4812 (Function generator physical address)
Remedy:
Set a physical address with a value other than zero.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
See also: p4812 (Function generator physical address)
202040
<location>Function generator: Illegal value for offset
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The value for the offset is higher than the value for the upper limit or lower than the value for the lower limit.
See also: p4826 (Function generator offset)
Remedy:
Adjust the offset value accordingly.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
See also: p4826 (Function generator offset), p4828 (Function generator lower limit), p4829 (Function generator upper
limit)
202041
<location>Function generator: Illegal value for bandwidth
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The bandwidth referred to the time slice clock cycle of the function generator has either been set too low or too high.
Depending on the time slice clock cycle, the bandwidth is defined as follows:
Bandwidth_max = 1 / (2 * time slice clock cycle)
Bandwidth_min = Bandwidth_max / 100000
Example:
Assumption: p4830 = 125 µs
--> Bandwidth_max = 1 / (2 * 125 µs) = 4000 Hz
--> Bandwidth_min = 4000 Hz / 100000 = 0.04 Hz
Note:
p4823: Function generator bandwidth
p4830: Function generator time slice clock cycle
See also: p4823 (Function generator bandwidth), p4830 (Function generator time slice cycle)
Remedy:
Check the value for the bandwidth and adapt accordingly.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
606
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
Alarms