SINAMICS alarms
205055
<location>Power circuit: Power units with different code numbers
Message value:
Parameter: %1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SIC_COMBI, SIC_SINUMERIK_828
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
The code numbers of the power units do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different power unit code number was detected.
Remedy:
For parallel circuit configurations, only power units with identical power unit data may be used.
205056
<location>Parallel circuit: Power unit EPROM versions differ
Message value:
Parameter: %1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SIC_COMBI, SIC_SINUMERIK_828
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
The EEPROM versions of the power units do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only power units with identical EEPROM versions may be used.
205057
<location>Parallel circuit: Power unit firmware versions differ
Message value:
Parameter: %1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SIC_COMBI, SIC_SINUMERIK_828
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
The firmware versions of the power units connected in parallel do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only power units with identical firmware versions may be used.
205058
<location>Parallel circuit: VSM EEPROM versions differ
Message value:
Parameter: %1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The EEPROM versions of the Voltage Sensing Modules (VSM) do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only Voltage Sensing Modules (VSM) with identical EEPROM versions may be used.
618
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
Alarms