201305
<location>Topology: Component number missing
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The component number from the topology was not parameterized (p0121 (for power unit, refer to p0107), p0131 (for
servo/vector drives, refer to p0107), p0141, p0151, p0161).
Fault value (r0949, interpret decimal):
The fault value includes the particular data set number.
Note:
The fault also occurs if speed encoders have been configured (p0187 to p0189) but no component numbers exist for
them.
In this case, the fault value includes the drive data set number plus 100 * encoder number (e.g. 3xx, if a component
number was not entered in p0141 for the third encoder (p0189)).
See also: p0121, p0131, p0141, p0142, p0151, p0186, p0187, p0188, p0189
Remedy:
Enter the missing component number or remove the component and restart commissioning.
See also: p0121, p0131, p0141, p0142, p0151, p0186, p0187, p0188, p0189
201306
<location>Firmware of the DRIVE-CLiQ component being updated
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
Firmware update is active for at least one DRIVE-CLiQ component.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component.
Remedy:
None necessary.
This alarm automatically disappears after the firmware has been updated.
201314
<location>Topology: Component must not be present
Message value:
Component number: %1, Component class: %2, Connection number: %3
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
For a component, "de-activate and not present" is set but this component is still in the topology.
Alarm value (r2124, interpret hexadecimal):
Byte 1: Component number
Byte 2: Component class of the component
Byte 3: Connection number
Note: Component class and connection number are described in F01375.
Remedy:
- remove the corresponding component.
- change the setting "de-activate and not present".
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. setpoint/
actual value comparison).
See also: p0105, p0125, p0145, p0155
530
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
Alarms