207801
<location>Drive: Motor overcurrent
Message value:
-
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The permissible motor limit current was exceeded.
- effective current limit set too low.
- current controller not correctly set.
- motor was braked with an excessively high stall torque correction factor.
- V/f operation: Up ramp was set too short or the load is too high.
- V/f operation: Short-circuit in the motor cable or ground fault.
- V/f operation: Motor current does not match the current of Motor Module.
Note:
Synchronous motor: Limit current= 1.3 * p0323
Induction motor: Limit current= 1.3 * r0209
Remedy:
- check the current limits (p0323, p0640).
- check the current controller (p1715, p1717).
- reduce the stall torque correction factor (p0326).
- increase the up ramp (p1318) or reduce the load.
- check the motor and motor cables for short-circuit and ground fault.
- check the Motor Module and motor combination.
207802
<location>Drive: Infeed or power unit not ready
Message value:
-
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
After an internal power-on command, the infeed or drive does not signal ready.
- monitoring time is too short.
- DC link voltage is not present.
- associated infeed or drive of the signaling component is defective.
- supply voltage incorrectly set.
Remedy:
- increase the monitoring time (p0857).
- ensure that there is a DC link voltage. Check the DC link busbar. Enable the infeed.
- replace the associated infeed or drive of the signaling component.
- check the line supply voltage setting (p0210).
See also: p0857 (Power unit monitoring time)
207805
<location>Drive: Power unit overload I2t
Message value:
-
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
NONE
Acknowledge:
NONE
Cause:
Alarm threshold for I2t overload (p0294) of the power unit exceeded.
The response parameterized in p0290 becomes active.
See also: p0290 (Power unit overload response)
Remedy:
- reduce the continuous load.
- adapt the load duty cycle.
- check the assignment of the rated currents of the motor and Motor Module.
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
SINAMICS alarms
665