Block %2 Selected Iso H/D Number %3 Does Not Match Tool %4; Block %2 Error %3 When Programming Tool Length Offset With Toff/Toffl; Block %2 Illegal Interpolation Type With Tool Length Compensation - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Remedy:
Correct the tool data of the active tool, or modify the part program in the case of error 7.
Alternatively, suppress all error alarms with the aid of MD20125 $MC_CUTMOD_ERR.
Program
Clear alarm with NC START or RESET key and continue the program.
Continuation:
14165
[Channel %1: ] Block %2 selected ISO H/D number %3 does not match tool %4
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = ISO H/D number
%4 = Tool number
Definitions:
When an H or D number is programmed in ISO_2 or ISO_3 mode, it must be available in the active tool. The active
tool may also be the last tool loaded on the master spindle or master toolholder. This alarm is output if there is no H
or D number on this tool.
Reaction:
Correction block is reorganized.
Local alarm reaction.
Interface signals are set.
Alarm display.
NC Stop on alarm at block end.
Remedy:
Set ISO H/D number correctly.
Program
Clear alarm with NC START or RESET key and continue the program.
Continuation:
14166
[Channel %1: ] Block %2 error %3 when programming a tool length offset with TOFF /
TOFFL
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = Error code
Definitions:
An error occurred while programming a tool length offset with TOFF or TOFFL. More information about the type of
error is given by the error code number:
Error code
1At least one tool length offset component has been programmed twice in one block (with TOFF).
2At least one tool length offset component has been programmed twice in one block (with TOFFL).
3Tool length offset components have been programmed in one block with both TOFF and TOFFL.
4An index must be declared when a tool length offset is programmed with TOFF, the form TOFF=.... is not permissible.
5An illegal index was declared when programming TOFFL (permissible values 1..3).
6An illegal axis was declared as the index when programming TOFF. Only geometry axes are permitted.
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Correct errors in program block.
Program
Clear alarm with NC START or RESET key and continue the program.
Continuation:
14170
[Channel %1: ] Block %2 illegal interpolation type with tool length compensation
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
If tool compensation (G43/G44) is activated in language mode ISO_M, the linear type of interpolation must be active.
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
NCK alarms
171