SINAMICS alarms
Remedy:
- check the electrical cabinet design and cable routing for EMC compliance
- for projects with the VECTOR drive object, check whether p0117 = 6 has been set on the Control Unit.
- increase the fault threshold (p7789).
See also: p0117 (Current controller computing dead time mode)
230010
<location>Power unit: Sign-of-life error cyclic data
Message value:
-
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828
Reaction:
NONE
Acknowledge:
NONE
Cause:
A DRIVE-CLiQ communication error has occurred between the Control Unit and the power unit involved.
The cyclic setpoint telegrams of the Control Unit were not received on time by the power unit for at least one clock
cycle.
Remedy:
- check the electrical cabinet design and cable routing for EMC compliance
230011
<location>Power unit: Line phase failure in main circuit
Message value:
-
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828
Reaction:
OFF2 (OFF1)
Acknowledge:
IMMEDIATELY
Cause:
A line phase failure was detected at the power unit.
- the fuse of a phase of a main circuit has ruptured.
- the DC link voltage ripple has exceeded the permissible limit value.
Note:
The cause may also be a phase failure in the motor feeder cable.
Remedy:
- check the main circuit fuses.
- check the motor feeder cables.
230012
<location>Power unit: Temperature sensor heat sink wire breakage
Message value:
%1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The connection to one of the heat sink temperature sensors in the power unit is interrupted.
Fault value (r0949, interpret hexadecimal):
Bit 0: Module slot (electronics slot)
Bit 1: Air intake
Bit 2: Inverter 1
Bit 3: Inverter 2
Bit 4: Inverter 3
Bit 5: Inverter 4
Bit 6: Inverter 5
Bit 7: Inverter 6
Bit 8: Rectifier 1
Bit 9: Rectifier 2
Remedy:
Contact the manufacturer.
692