Topology: Comparison Serial Number Of A Component Is Different; Topo: Comparison Connection Of A Component Is Different - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Remedy:
Check the component soft-wired connections against the hardware configuration of the drive unit in the commissioning
software and correct differences.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. setpoint/
actual value comparison).
201425
<location>Topology: Comparison serial number of a component is different
Message value:
Component number: %1, Component class: %2, Differences: %3
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected differences in the actual and target topologies in relation to one component.
The serial number is different.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
cc = number of differences
bb = component class
aa = component number of the component
Note:
The component class is described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting the topologies:
- change over the actual topology to match the target topology.
- download the target topology that matches the actual topology (commissioning software).
Re byte cc:
cc = 1 --> can be acknowledged using p9904 or p9905.
cc > 1 --> can be acknowledged using p9905 and can be de-activated using p9906 or p9907/p9908.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. setpoint/
actual value comparison).
See also: p9904 (Topology comparison, acknowledge differences), p9905 (Device specialization), p9906 (Topology
comparison, comparison stage of all components), p9907 (Topology comparison, comparison stage of the component
number), p9908 (Topology comparison, comparison stage of a component)
201428
<location>Topo: Comparison connection of a component is different
Message value:
Component number: %1, Component class: %2, Connection number1: %3, Connection number2: %4
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected differences in the actual and target topologies in relation to one component. A
component was connected to another connection.
The different connections of a component are described in the alarm value:
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number of the target topology
cc = connection number of the actual topology
bb = component class
aa = component number
Note:
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
SINAMICS alarms