NCK alarms
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Locate the position of the intermediate point with the parameters I, J and K in such a way that it actually is located
between the initial and end points of the circle or do not make use of this type of circle programming and instead pro-
gram the circle with radius or opening angle or center point parameters.
Program
Clear alarm with NC START or RESET key and continue the program.
Continuation:
15030
[Channel %1: ] Block %2 different measurement system settings
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
The INCH or METRIC instruction describes the system of measurement in which the data blocks have been read from
the control. In order to prevent the incorrect interpretation of data intended for a particular system of measurement, a
data block is only accepted if the above instruction matches the active system of measurement.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Change the system of measurement or load a data block which matches the system of measurement.
Program
Clear alarm with the RESET key. Restart part program
Continuation:
15100
[Channel %1: ] Block %2 REORG abort caused by log file overflow
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
In order to synchronize the preprocessing run and the main run with REORG, the control accesses modification data
which are maintained in a logfile. The alarm indicates that no more capacity is available in the logfile for the specified
block in the channel.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Please inform the authorized personnel/service department. No remedial measures are available for the further exe-
cution of the current part program, however:
1. Reduce log file size requirement by:
Reducing the distance between the preprocessing and the main run via appropriate preprocessing stops STOPRE.
2. Increase the size of the logfile by means of the channel-specific machine data:
Modify MD28000 $MC_MM_REORG_LOG_FILE_MEM and
Modify MD 28010 $MC_MM_NUM_REORG_LUD_MODULES
Program
Clear alarm with the RESET key. Restart part program
Continuation:
15110
[Channel %1: ] Block %2 REORG not possible
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
In order to synchronize the preprocessing run and the main run with REORG, the control accesses modification data
which are maintained in a logfile. The alarm indicates that no more capacity is available in the logfile for the specified
block in the channel.
The alarm message means that the logfile has been deleted in order to obtain additional memory for program reorga-
nization. Consequently, it is no longer possible to REORG the preprocessing memory up to the next coincidence point.
204
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
Alarms