Contactor Feedback Signal "Closed" Missing; Contactor Feedback Signal "Open" Missing; Arm. Short-Circuit/Internal Voltage Protection: Parameterization Error - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

SINAMICS alarms
207904
<location>External armature short-circuit: Contactor feedback signal "Closed"
missing
Message value:
-
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828
Reaction:
NONE
Acknowledge:
NONE
Cause:
When closing, the contactor feedback signal (p1235) did not issue the signal "Closed" (r1239.1 = 1) within the moni-
toring time (p1236).
Remedy:
- check that the contactor feedback signal is correctly connected (p1235).
- check the logic of the contactor feedback signal (r1239.1 = 1: "Closed", r1239.1 = 0: "Open").
- increase the monitoring time (p1236).
- if required, set the external armature short-circuit without contactor feedback signal (p1231=2).
207905
<location>External armature short-circuit: Contactor feedback signal "Open" missing
Message value:
-
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
When opening, the contactor feedback signal (p1235) did not issue the signal "Open" (r1239.1 = 0) within the moni-
toring time (p1236).
Remedy:
- check that the contactor feedback signal is correctly connected (p1235).
- check the logic of the contactor feedback signal (r1239.1 = 1: "Closed", r1239.1 = 0: "Open").
- increase the monitoring time (p1236).
- if required, set the external armature short-circuit without contactor feedback signal (p1231=2).
207906
<location>Armature short-circuit / internal voltage protection: Parameterization error
Message value:
Fault cause: %1, motor data set: %2
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The armature short-circuit is incorrectly parameterized.
Fault value (r0949, interpret decimal):
Low word: Motor data set number
High word: Cause:
1: A permanent-magnet synchronous motor has not been selected.
2: No induction motor selected.
101: External armature short-circuit: Output (r1239.0) not connected up.
102: External armature short-circuit with contactor feedback signal: No feedback signal connected (BI:p1235).
103: External armature short-circuit without contactor feedback signal: Delay time when opening (p1237) is 0.
201: Internal voltage protection: The maximum output current of the Motor Module (r0209) is less than 1.8 * motor
short-circuit current (r0331).
202: Internal voltage protection: A Motor Module in booksize or chassis format is not being used.
203: Internal voltage protection: The motor short-circuit current (p0320) is greater than the maximum motor current
(p0323).
204: Internal voltage protection: The activation (p1231 = 4) is not given for all motor data sets with synchronous motors
(p0300 = 2xx, 4xx).
672
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
Alarms