<location>Function generator: Drive specified a multiple number of times
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The drive object specified for connection is already specified.
Alarm value (r2124, interpret decimal):
Drive object number of the drive object that is specified a multiple number of times.
Remedy:
Specify a different drive object.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
202009
<location>Function generator: Illegal mode
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The set operating mode (p1300) of the drive object is not permissible when using the function generator.
Alarm value (r2124, interpret decimal):
Number of the drive object involved.
Remedy:
Change the operating mode for this drive object to p1300 = 20 (encoderless speed control) or p1300 = 21 (speed con-
trol with encoder).
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
202010
<location>Function generator: Speed setpoint from the drive is not zero
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The speed setpoint of a drive selected for connection is greater than the value for the standstill detection set using
p1226.
Remedy:
For all of the drives specified for connection, set the speed setpoints to 0.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
SINAMICS alarms
603