<location>BICO: Interconnections to inactive objects exceeded
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum number of BICO interconnections (signal sinks) when de-activating a drive object was exceeded.
When de-activating a drive object, all BICO interconnections (signal sinks) are listed in the following parameters:
- r9498[0...29]: List of the BI/CI parameters involved.
- r9499[0...29]: List of the associated BO/CO parameters.
Remedy:
The alarm automatically disappears as soon as no BICO interconnection (value = 0) is entered in r9498[29] and
r9499[29].
Notice:
When re-activating the drive object, all BICO interconnections should be checked and if required, re-established.
201510
<location>BICO: Signal source is not float type
Message value:
Parameter: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested connector output does not have the correct data type. This interconnection is not established.
Fault value (r0949, interpret decimal):
Parameter number to which an interconnection should be made (connector output).
Remedy:
Interconnect this connector input with a connector output having a float data type.
201511
<location>BICO: Interconnection between different scalings
Message value:
Parameter: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested interconnection was established. However, a conversion is made between the BICO output and BICO
input using the reference values.
- the BICO output has different normalized units than the BICO input.
- message only for interconnections within a drive object.
Example:
The BICO output has, as normalized unit, voltage and the BICO input has current.
This means that the factor p2002 (contains the reference value for current) / p2001 (contains the reference value for
voltage) is calculated between the BICO output and BICO input.
Fault value (r0949, interpret decimal):
Parameter number of the BICO input (signal sink).
Remedy:
No correction needed.
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
SINAMICS alarms
555