Program
Clear alarm with the RESET key. Restart part program
Continuation:
61215
[Channel %1: ] Block %2: Unfinished dimension incorrectly programmed
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
Check the blank spigot dimensions. The blank spigot must be larger than the production part spigot.
Alarm triggered by following cycles: CYCLE76, CYCLE77, E_PI_CIR, E_PI_REC, E_PO_CIR, E_PO_REC,
F_PI_CIR, F_PI_REC, F_PO_CIR, F_PO_REC
Remedy:
Check parameters _AP1 and _AP2.
61216
%[[Channel %1: ] Block %2: %]Feed/tooth only possible with cutting tools
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
Feed per tooth is only possible with milling tools.
Alarm triggered by following cycles: E_TFS, F_TFS.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
As alternative, set a different feed type.
Program
Clear alarm with the RESET key. Restart part program
Continuation:
61217
[Channel %1: ] Block %2: Cutting speed programmed for tool radius 0
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
To be able to work with cutting speed, the tool radius has to be specified.
Alarm triggered by following cycles: E_DR_SIN, E_DR_TAP, E_TFS, F_DR_SIN, F_DR_TAP, F_DRILLC,
F_DRM_TA, F_TAP, F_TFS
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Enter a value for cutting speed.
Program
Clear alarm with the RESET key. Restart part program
Continuation:
61218
[Channel %1: ] Block %2: Feed/tooth programmed, but number of tools equals zero
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
For feed per tooth, the number of teeth has to be specified.
Alarm triggered by following cycles: E_TFS, E_DR_BGF, F_TFS.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
NCK alarms
407