SINAMICS alarms
202075
<location>Trace: Pretrigger time too long
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected pretrigger time must be shorter than the trace time.
See also: p4721 (Trace recording time), p4722 (Trace trigger delay)
Remedy:
Check the pretrigger time setting and change if necessary.
202080
<location>Trace: Parameterization deleted due to unit changeover
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The trace parameterization in the drive unit was deleted due to a unit changeover or a change in the reference param-
eters.
Remedy:
Restart trace.
202099
<location>Trace: Insufficient Control Unit memory
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory space still available on the Control Unit is no longer sufficient for the trace function.
Remedy:
Reduce the memory required, e.g. as follows:
- reduce the trace time.
- increase the trace clock cycle.
- reduce the number of signals to be traced.
See also: r4708 (Trace memory space required), r4799 (Trace memory location free)
202100
<location>CU: Computing dead time current controller too short
Message value:
%1
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
NONE
Acknowledge:
NONE
Cause:
The value in p0118 produces a dead time of one clock cycle because it is prior to setpoint availability. A possible cause
could be, for example, that the system characteristics no longer match those parameterized after a component has
been replaced.
Alarm value (r2134, floating point):
The minimum value for p0118 where a dead time no longer occurs.
Remedy:
- set p0118 to a value greater than or equal to the alarm value.
- set p0117 to an automatic setting.
- check the firmware releases of the components involved.
See also: p0117 (Current controller computing dead time mode), p0118 (Current controller computing dead time)