SINAMICS alarms
201914
<location>COMM INT: Monitoring time configuration expired
Message value:
%1
Drive object:
All objects
Reaction:
Servo: OFF1 (NONE, OFF2, OFF3)
Infeed: OFF1 (NONE, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The monitoring time for the configuration has expired.
Fault value (r0949, interpret decimal):
0: The transfer time of the send configuration data has been exceeded.
1: The transfer time of the receive configuration data has been exceeded.
Remedy:
- acknowledge faults that are present.
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
201915
<location>IF1: PB/PN clock cycle synchronous operation sign-of-life failure drive
object 1
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Group display for problems with the sign-of-life of the master (clock-cycle synchronous operation) on the drive object
1 (Control Unit).
For central measurements, synchronism with the central master is lost.
Remedy:
Note:
IF1: Interface 1
PB: PROFIBUS
PN: PROFINET
201920
<location>PROFIBUS: Interruption cyclic connection
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The cyclic connection to the PROFIBUS master is interrupted.
Remedy:
Establish the PROFIBUS connection and activate the PROFIBUS master in the cyclic mode.
596
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
Alarms