Excitation Current Outside The Tolerance Range; Flux Out Of Tolerance; Three-Phase Setpoint Generator Operation Selected/Active - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

207913
<location>Excitation current outside the tolerance range
Message value:
-
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The difference between the excitation current actual value and setpoint has exceeded the tolerance:
abs(r1641 - r1626) > p3201 + p3202
The cause of this fault is again reset for abs(r1641 - r1626) < p3201.
Remedy:
- check the parameterization (p1640, p3201, p3202).
- check the interfaces to the excitation equipment (r1626, p1640).
- check the excitation equipment.
207914
<location>Flux out of tolerance
Message value:
-
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The difference between the flux actual value and setpoint has exceeded the tolerance:
abs(r0084 - r1598) > p3204 + p3205
The cause of this fault is again reset for abs(r0084 - r1598) < p3204.
The fault is only issued after the delay time in p3206 has expired.
Remedy:
- check the parameterization (p3204, p3205).
- check the interfaces to the excitation equipment (r1626, p1640).
- check the excitation equipment.
- check the flux control (p1592, p1592, p1597).
- check the control for oscillation and take the appropriate counter measures (e.g. optimize the speed control loop,
parameterize a bandstop filter).
207918
<location>Three-phase setpoint generator operation selected/active
Message value:
-
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828
Reaction:
NONE
Acknowledge:
NONE
Cause:
Only for separately excited synchronous motors (p0300 = 5):
The actual open-loop/closed-loop control mode is I/f control (open-loop) with a fixed current (p1300 = 18).
The speed is entered via the setpoint channel and the current setpoint is given by the minimum current (p1620).
It must be ensured that in this mode, the control dynamic performance is very limited. This is the reason that longer
ramp-up times should be set for the setpoint speed than for normal operation.
Remedy:
Select another open-loop/closed-loop control mode
See also: p1300 (Open-loop/closed-loop control operating mode)
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
SINAMICS alarms
675