<location>Drive: DSC without encoder not possible
Message value:
-
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The function DSC (Dynamic Servo Control) was activated although there is no encoder.
See also: p1191 (DSC position controller gain KPC)
Remedy:
If there is no encoder and connector input p1191 (DSC position controller gain) is interconnected, then connector input
p1191 must have a 0 signal.
207430
<location>Drive: Changeover to open-loop torque controlled operation not possible
Message value:
-
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
For encoderless operation, the converter cannot change over to closed-loop torque-controlled operation (BI: p1501).
Remedy:
Do not attempt to cover over to closed-loop torque-controlled operation.
207431
<location>Drive: Changeover to encoderless operation not possible
Message value:
-
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
OFF2 (OFF1)
Acknowledge:
IMMEDIATELY
Cause:
For closed-loop torque control, the converter cannot change over to encoderless operation (p1404).
Remedy:
Do not attempt to change over to encoderless operation.
207432
<location>Drive: Synchronous motor without overvoltage protection
Message value:
%1
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
OFF2 (OFF1)
Acknowledge:
IMMEDIATELY
Cause:
Under voltage conditions, a synchronous motor can generate an overvoltage condition that can destroy the drive sys-
tem.
Fault value (r0949, interpret hexadecimal):
Associated Drive Data Set (DDS).
Remedy:
Overvoltage protection can be implemented in the following ways:
- limit the maximum speed (p1082) without any additional protection.
The maximum speed without protection is calculated as follows:
Rotary motors: p1082 [rpm] <= 11.695 * p0297/p0316 [Nm/A]
Linear motors: p1082 [m/min] <= 73.484 * p0297/p0316 [N/A]
- use a voltage protection module (VPM) in conjunction with the function "Safe Torque Off" (p9601, p9801).
When a fault condition exists, the VPM short-circuits the motors. During the short-circuit, the pulses must be sup-
pressed - this means that the terminals for the function "Safe Torque Off" must be connected to the VPM.
When using a VPM, p0643 must be set to 1.
- activating the internal voltage protection (IVP) with p1231 = 3.
See also: p0643 (Overvoltage protection for synchronous motors), p1231 (Armature short-circuit / DC brake configu-
ration)
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
SINAMICS alarms
651