[Channel %1: ] Action %2<ALNX> not allowed in current mode
Parameters:
%1 = Channel number
%2 = Action number/action name
Definitions:
A different operating mode must be activated for the activated function.
Reaction:
Alarm display.
Remedy:
Check operation and operating state.
Program
Clear alarm with the Delete key or NC START.
Continuation:
16911
[Channel %1: ] Mode change is not allowed
Parameters:
%1 = Channel number
Definitions:
The change from overstoring into another operating mode is not allowed.
Reaction:
Alarm display.
Remedy:
After overstoring is terminated, it is possible to change to another operating state again.
Program
Clear alarm with the Delete key or NC START.
Continuation:
16912
[Channel %1: ] Program control: action %2<ALNX> only possible in reset state
Parameters:
%1 = Channel number
%2 = Action number/action name
Definitions:
This action can only be performed in Reset state.
Example: Program selection through HMI or channel communication (INIT) can only be performed in Reset state.
Reaction:
Alarm display.
Remedy:
Reset or wait until processing is terminated.
Program
Clear alarm with the Delete key or NC START.
Continuation:
16913
[Mode group %1: ] [Channel %2: ] Mode change: action %3<ALNX> not allowed
Parameters:
%1 = Channel number
%2 = Mode group number
%3 = Action number/action name
Definitions:
The change to the desired mode is not permitted. The change can only take place in the Reset state.
Example:
Program processing is halted in AUTO mode by NC Stop. Then there is a mode change to JOG mode (program status
interrupted). From this operating mode, it is only possible to change to AUTO mode and not to MDI mode!
Reaction:
Alarm display.
Remedy:
Either activate the Reset key to reset program processing, or activate the mode in which the program was being pro-
cessed previously.
Program
Clear alarm with the Delete key or NC START.
Continuation:
16914
[Mode group %1: ] [Channel %2: ] Mode change: action %3<ALNX> not allowed
Parameters:
%1 = Channel number
%2 = Mode group number
%3 = Action number/action name
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
NCK alarms
251