<location>Encoder 2: Amplitude error monitoring track A + B
Message value:
Amplitude: %1, Angle: %2
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
OFF1 (IASC/DCBRAKE, NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The amplitude of the rectified encoder signals A and B and the amplitude from the roots of A^2 + B^2 for encoder 2
are not within the tolerance bandwidth.
Fault value (r0949, interpret hexadecimal):
yyyyxxxx hex:
yyyy = Signal level, track B (16 bits with sign).
xxxx = Signal level, track A (16 bits with sign).
The nominal signal level of the encoder must lie in the range 375 mV to 600 mV (500 mV -25/+20 %).
The response thresholds are < 176 mV (observe the frequency response of the encoder) and > 955 mV.
A signal level of 500 mV peak value corresponds to the numerical value 5333 hex = 21299 dec.
Note:
The analog values of the amplitude error are not measured at the same time with the hardware fault output by the
Sensor Module.
Remedy:
- check that the encoder cables and shielding are routed in compliance with EMC.
- check the plug connections
- replace the encoder or encoder cable
- check the Sensor Module (e.g. contacts).
232117
<location>Encoder 2: Inversion error signals A and B and R
Message value:
Fault cause: %1 bin
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
OFF1 (IASC/DCBRAKE, NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
For a square-wave encoder (bipolar, double ended) the A* and B* and R* signals are not inverted with respect to sig-
nals A and B and R.
Fault value (r0949, interpret binary):
Bits 0-15: Only for internal Siemens troubleshooting.
Bit 16: Error track A.
Bit 17: Error track B.
Bit 18: Error track R.
Note:
For SMC30 (order no.. 6SL3055-0AA00-5CA0 and 6SL3055-0AA00-5CA1 only), CUA32, and CU310, the following
applies:
A square-wave encoder without track R is used and track monitoring (p0405.2 = 1) is activated.
Remedy:
Check the encoder/cable: Does the encoder provide signals and the associated inverted signals?
Note:
For SMC30 (order no. 6SL3055-0AA00-5CA0 and 6SL3055-0AA00-5CA1 only), the following applies:
- check the setting of p0405 (p0405.2 = 1 is only possible if the encoder is connected at X520).
For a square-wave encoder without track R, the following jumpers must be set for the connection at X520 (SMC30) or
X23 (CUA32, CU310):
- pin 10 (reference signal R) <--> pin 7 (encoder power supply, ground)
- pin 11 (reference signal R inverted) <--> pin 4 (encoder power supply)
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
SINAMICS alarms
775