15420
[Channel %1: ] Block %2 instruction in current mode not allowed
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
The alarm is output in the following situations:
- The interpreter has detected an illegal instruction (e.g. a motion command) while processing an INI file or a definition
file (macro or GUD).
- In a GUD file, the access security for a machine data item is to be changed with REDEF, although
an ACCESS file (_N_SACCESS_DEF, _N_MACCESS_DEF, _N_UACCESS_DEF) is available.
Access rights for machine data can then only be changed via one of the ACCESS files with REDEF.
- When processing the safety initialization program /_N_CST_DIR/_N_SAFE_SPF an illegal instruction was detected
due to the reduced language scope configured.
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
- Correct the INI, GUD or macro file.
- Correct part program.
Program
Clear alarm with NC START or RESET key and continue the program.
Continuation:
15450
[Channel %1: ] Block %2 compiled program cannot be stored
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
In the compile mode, a compiled program could not be stored. One of the following reasons applies:
- Not enough memory
- Intermediate code line (compilate) too large
Reaction:
Alarm display.
Remedy:
Create space in work memory or modify part program (make it less complex).
Program
Clear alarm with the Delete key or NC START.
Continuation:
15460
[Channel %1: ] Block %2 syntax error when locking
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
The addresses programmed in the block are not compatible with the modal syntax-determining G function.
Example:
N100 G01 ... I .. J.. K.. LF
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Correct the displayed block and ensure that the G functions and addresses in the block are in agreement.
Program
Clear alarm with NC START or RESET key and continue the program.
Continuation:
15500
[Channel %1: ] Block %2 illegal angle of shear
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
The function CSHEAR has been called with an illegal (impossible) angle of shear, e.g. when the sum of angles
between the axis vectors is greater than 360 degrees.
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
NCK alarms
215