201112
<location>CU: Power unit not permissible
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The connected power unit cannot be used together with this Control Unit.
Fault value (r0949, interpret decimal):
1: Power unit is not supported (e.g. PM240).
2: DC/AC power unit connected to CU310 not permissible.
Remedy:
Replace the power unit that is not permissible by a component that is permissible.
201120
<location>Terminal initialization has failed
Message value:
%1
Drive object:
All objects
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
An internal software error occurred while the terminal functions were being initialized.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
- replace the Control Unit.
201122
<location>Frequency at the measuring probe input too high
Message value:
%1
Drive object:
All objects
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The frequency of the pulses at the measuring probe input is too high.
Fault value (r0949, interpret decimal):
1: DI/DO 9 (X122.10/X132.2)
2: DI/DO 10 (X122.12/X132.3)
4: DI/DO 11 (X122.13/X132.4)
8: DI/DO 13 (X132.10)
16: DI/DO 14 (X132.12)
32: DI/DO 15 (X132.13)
64: DI/DO 8 (X122.9/X132.1)
128: DI/DO 12 (X132.9)
To the terminal designation:
The first designation is valid for CU320, the second for CU305
Remedy:
Reduce the frequency of the pulses at the measuring probe input.
524
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
Alarms